tryckfallets påverkan vid energimätning

Relevanta dokument
raksträckor för ultrajudsmätare rapport 2011:11

provprogram för värmeväxlare och vattenvärmare Tekniska bestämmelser F:109 Mars 2004

Kundcentraler och energimätare

raksträckor för större ultraljudsmätare rapport 2013:12

TEMPERATURMÄTNING I VÄTSKEFLÖDEN. rapport 2015:118

TERMISKA ENERGIMÄTARE MED KORTA INTEGRERINGSTIDER

INSTRUKTIONER FÖR INSTALLATÖRER. Uppdaterad version LOKALA REGLER FÖR ATT ANSLUTA TILL VÄXJÖS FJÄRRKYLNÄT EN DEL AV DIN VARDAG

HYDRAULIK Rörströmning I

kavitation i styrventiler Rapport I 2009:45

Siemens AB Upplands Väsby. Följande data gäller för provobjektet. (se bilaga 2)

Injusteringsventil PVM

PVM 15-50, Differenstryckspaket

Technical description with installation and maintenance instructions

certifiering av avstängningsventiler program för provning och kontroll

RADIATORTERMOSTATER RUMSTEMPERATUR TILLOPPSTEMPERATUR TRYCKFÖRHÅLLANDEN

BROEN BALLOREX DP. Differenstryckregulator

Viktig information för transmittrar med option /A1 Gold-Plated Diaphragm

Tryckmätningar på standardkylskåpet ER8893C

Små värmekällor kunder som prosumenter

PREFABRICERADE ENHETER

Mätning och utvärdering av borrhålsvärmeväxlare Distribuerad Termisk Respons Test och uppföljning av bergvärmepumpsinstallationer i Hålludden

Injusteringsventiler. Thermotech MultiSystem FÖRDELAR FAKTA

Wirsbo Golvvärme Wirsbo Push 20/25

US-S/FFL. Energimätare av ultraljudstyp. Funktion. Flexibel uppbyggnad. Anslutning. Montering. Hög tillförlitlighet

Diagnostiskt prov i mätteknik/luftbehandling inför kursen Injustering av luftflöden

Kontaktperson Datum Beteckning Sida Mathias Johansson P (4) Energiteknik mathias.johansson.et@sp.

GOLD SD Med styrenhet/with control unit. Fläkt/ Fan. Utan filter/ Without filter. Fläkt/Fan. Fläkt/ Fan. Med filter/ With filter.

HYDRAULIK Rörströmning IV

Vi ger dig MER genom att ge dig MINDRE

TTM Shuntopac. Drift- och skötselanvisning Kombishuntar

V232. Venta. Tvåvägs balanserad kägelventil, PN 25

Konsoliderad version av. Styrelsens för ackreditering och teknisk kontroll (SWEDAC) föreskrifter och allmänna råd (STAFS 2006:8) om värmemätare

Automatisk stamregulator ASV-P Avstängningsventil ASV-M

Differenstryckventil. Thermotech MultiSystem FÖRDELAR FAKTA

AMTRON SONIC D. Kompakt energimätare av ultraljudstyp

UltraE Ultrasonisk Energimätare

GOLD SD Fläkt 2/ Fan 2. Fläkt 1/ Fan 1. Fläkt/ Fan. Utan filter/ Without filter. Fläkt 1/ Fan 1. Fläkt 2/ Fan 2. Med filter/ With filter Filter

Version 1, Februari Kravspecifikation för omblandande tilluftsdon i CAV-system

Ingjuten sensor för mätning av uttorkningsförlopp beräkning av inverkan av sensorns dimension och orientering. Sensobyg delprojekt D4

Roth Golvvärmesystem. Roth Golvvärmecentral, GVC. ... living full of energy! Projekterings- och Monteringsanvisningar

ett nytt steg i energiforskningen

värmemätare dynamisk funktionskontroll av värmemätare för småhus Tekniska bestämmelser F:111 Mars 2004

Injusteringsventiler ESBE 2001/2002 SE

US-WV. Energimätare av ultraljudstyp. Funktion. Hög tillförlitlighet. Anslutning. Flexibel uppbyggnad. Montering

Differenstrycksregulator (PN 16) AVPL monteras i returen, justerbar inställning

Internationell utblick Hot spots i Europa för ny fjärrvärmeutbyggnad. Vilka innovationer behöver fjärrvärmen?

TA-PICL. Tryckoberoende reglerkrets ENGINEERING ADVANTAGE

Handlingarna skall således omfatta funktionsbeskrivning på både primär- och sekundärsystemet.

Kontaktperson Datum Beteckning Sida Mathias Johansson P (4) Energiteknik

DIFFERENSTRYCKSREGULATORER

- tillopps- eller returledningsmonterad, justerbar inställning AVP-F - returledningsmonterad, fast inställning AVP-F

Tekniska bestämmelser för Mätarplats Kyla

HYDRAULIK Rörströmning IV

Differenstrycksregulator (PN 16) AVPL - monteras i returen, justerbar inställning

UPONOR VVS GOLVVÄRME UPONOR PUSH 45U/ PUSH 45U ELECTRONIC. Uponor Push 45U/ Uponor Push 45U Electronic

GOLD SD Med styrenhet/with control unit. Fläkt 1A/B/ Fan 1A/B. Fläkt 2A/B/ Fan 2A/B. Fläkt/ Fan. Utan filter/ Without filter

BALLOREX venturi 4.1 Inledning

Boiler with heatpump / Värmepumpsberedare

fakta mätteknik Kortfattad fakta lufthastighet och -flöde, givarsystem, mätmetoder etc. fakta - kunskap - utbildning - support

Styrelsens för ackreditering och teknisk kontroll författningssamling

Kan framtidens byggnader klara sig utan energiförsörjningssystem?

Rörkopplingsenhet STD-05 Specifikation och monteringsanvisning

Fjärrvärmecentraler och energimätare. 30 september - 1 oktober, 2014 Elmia, Jönköping

Differenstrycksregulator (PN 25) AVP - tillopps- eller returledningsmonterad, justerbar inställning

fjärvärmecentraler 10 år håller de måttet? rapport 2011:9

Åby Nordgård samfällighetsförening. VärmeProjektet

Differenstrycksregulator (PN 16) AHP - retur montering, justerbar inställning

Differenstrycksregulator med flödesbegränsning och integrerad reglerventil (PN 16) AHPBM-F tilloppsmontering, fast inställning

Kundcentraler och energimätare

Fjärrkyla med hjälp av överskottsvärme Ilkka Salo

RADIATORTERMOSTATER RUMSTEMPERATUR TILLOPPSTEMPERATUR TRYCKFÖRHÅLLANDEN

Självkörande bilar. Alvin Karlsson TE14A 9/3-2015

Flödesregulator med inbyggd reglerventil (PN 16, 25, 40) AFQM, AFQM 6 retur- och tilloppsmontering

Sammanfattning hydraulik

Kontaktperson Datum Beteckning Sida Mathias Johansson P (4) Energiteknik

Förbättringsguide fjärrkyla. Anpassning av befi ntliga kylsystem till fjärrkyla

PV Compact , Differenstrycksventil

BALLOREX DP 6.1 Inledning

STA-DR ROT-PRODUKTER INJUSTERING. RATT Det inställda värdet är avläsbart på digitalratten, som säkerställer en

FASTBRÄNSLEPRODUKTER FASTBRÄNSLEPRODUKTER

PRODUKTBLAD Mätinstrument sida 1 av 5

DN (mm) k vs (m 3 /h) Anslutning. 1,6 Cylindr. gänga. enl. ISO. 25 8,0 Flänsar PN 25, 20 6,3 003H H6352. DN (mm) Anslutning 1,6. Cylindr.

Dimensionering av kulsektorventiler och sätesventiler för kontinuerlig reglering

TBV-CM. Terminalventil för modulerande reglering ENGINEERING ADVANTAGE

Jämförelse av Solhybrider

Projektarbete Kylska p

Nätverksträff för energieffektivisering och energitjänster

Differenstrycksregulator (PN 16) AVP

SÅ LYCKAS VI MED ENERGIBESPARINGAR I ISHALLAR

Kalibrering. Lars Andersson. - Intertek reder ut begreppen. Technical Manager, Intertek

STAD-R. Injusteringsventiler DN med reducerat Kv

MÄTNING AV VÄGT REDUKTIONSTAL MEASUREMENT OF THE WEIGHTED SOUND TRANSMISSION LOSS

TBV-CM. Styrventiler med injusteringsfunktion för mindre apparater För modulerande reglering

TA-PICL. Shuntgrupper Tryckoberoende reglerkrets

Helautomatisk injusteringsventil CIM 790

TA-PICL. Prefabricerade enheter Tryckoberoende reglerkrets

GOLD SD eff.var./cap.var.120-1

Kontaktperson Datum Beteckning Sida Mathias Johansson P (4) Energiteknik mathias.johansson.et@sp.

Flödesregulator med inbyggd reglerventil (PN 16) AHQM retur- och tilloppsmontering

FORTA M315. Installation. 218 mm.

Transkript:

tryckfallets påverkan vid energimätning rapport 2013:11 Figur 4. Montering av temperaturgivare. Mätningarna gjordes vid två olika temperatur mätningarna med tiogradigt vatten var testrig inte skulle påverkas av omgivningstemperatu mätning med tiogradigt vatten. Figur 5. Testrigg, isolerad inför mätning med ti Mätning av temperaturskillnad före och efte differenstryck nära noll (med fullt öppen in 2, 4 och 8 bar. Flödet hölls konstant vid samtliga mätni 3.1 Redovisad mätosäkerhet Mätosäkerheten har uppskattats till bättre ä Differenstryck ±1 kpa Temperatur ±0,03 C Flöde ±1,5%

Tryckfallets påverkan vid energimätning MARKUS ALSBJER SARA JENSEN ISBN 978-91-7381-109-5 2013 Svensk Fjärrvärme AB

FÖRORD Syftet med det här projektet är att verifiera att teori och praktik stämmer avseende den energi som frigörs av att tryckfallet över styrventilen omvandlas till värme och därmed medför en temperaturökning av vattnet. Detta påverkar energimätningen och om temperaturskillnaden mellan fram- och returledningen är liten i kombination med ett stort tryckfall över styrventilen så är påverkan inte försumbar. Eftersom temperaturskillnaden mellan fram- och returledningen är stor i fjärrvärmesystem och liten i fjärrkylasystem, så är det bara i fjärrkylasystem som tryckfallets påverkan på energimätningen kan vara ett problem. Eftersom tryckfallet över styrventilen behöver vara stort för att påverkan på energimätningen inte skall vara försumbar så är det främst i stora fjärrkylasystem där differenstrycken, skillnaden mellan trycket i fram- och returledningen, är stor som detta kan inträffa. Detta gäller för områden nära pumpstationer eller produktionsanläggningar vid höglast så problemet är begränsat både i tid och i rum. Resultaten från projektet kommer att beaktas vid uppdateringen av Svensk Fjärrvärmes tekniska bestämmelser. Projektet har genomförts av Markus Alsbjer och Sara Jensen, SP Sveriges Tekniska Forskningsinstitut. Till projektet har en referensgrupp varit knuten bestående av Holger Feurstein Lunds Energikoncernen AB, Marie Skogström One Nordic AB och Torsten Olsson Göteborg Energi AB. Projektet ingår i forskningsprogrammet Fjärrsyn som finansieras gemensamt av Energimyndigheten och fjärrvärmebranschen. Forskningen inom Fjärrsyn ska stärka fjärrvärme och fjärrkyla, uppmuntra konkurrenskraftig affärs- och teknikutveckling och skapa resurseffektiva lösningar för framtidens hållbara energisystem till nytta för fjärrvärmebranschen, kunderna, miljön och samhället i stort. Bo Johansson Ordförande i Svensk Fjärrvärmes teknikråd Rapporten redovisar projektets resultat och slutsatser. Publicering innebär inte att Fjärrsyns styrelse eller Svensk Fjärrvärme har tagit ställning till innehållet. 4

SAMMANFATTNING Energi byter form när vatten flödar genom en styrventil. Den energi som frigörs när trycket faller över styrventilen omvandlas till värme. Teoretiska beräkningar gjorda av Bo Frank (Frank) stämmer väl överens med de uppmätta värdena i detta projekt. All den energi som omvandlas när trycket faller över en styrventil värmer vattnet. Tabell 1. Sammanställning av temperaturskillnader vid olika differenstryck. ΔP (bar) Uppmätt ΔT vid rumstemperatur Uppmätt ΔT vid 10 C Beräknat ΔT 0,0-0,02-0,02 0,00 2,0 0,05 0,03 0,04 4,0 0,07 0,07 0,08 8,0 0,17 0,16 0,17 I fjärrvärmesystem är temperaturökningen försumbar på grund av stora temperaturskillnader mellan fram- och returledning, men i fjärrkylasystem kan temperaturökningen från tryckfallet över styrventilen påverka energimätningen så mycket att det inte alls är försumbart. I fjärrkylasystem är temperaturskillnaderna mellan framledning och retur små och differenstrycken höga och då gör det skillnad om retursidans temperaturgivare placeras före eller efter styrventilen. Till exempel innebär en temperaturdifferens på 3 K och 5 bars tryckfall över styrventilen att det blir 3,4 % skillnad om man mäter temperaturen före eller efter styrventilen. 5

SUMMARY Energy changes form when water flows through a control valve. The energy released when the pressure drops over the control valve is converted into heat. Theoretical calculations made by Bo Frank (Frank) comply well with the measured values in this project. All the energy converted when the pressure drops across a control valve is heating the water. Table 2. Summary of temperature differences at various differential pressures. ΔP (bar) Measured ΔT, room temperature Measured ΔT, 10 C Calculated ΔT 0.0-0.02-0.02 0.00 2.0 0.05 0.03 0.04 4.0 0.07 0.07 0.08 8.0 0.17 0.16 0.17 In district heating systems, the temperature increase is negligible because of the large temperature difference between supply and return line. But in district cooling systems, the temperature increase from the pressure drop over the control valve affect the energy measurement so much that it is not at all negligible. In district cooling systems the temperature difference between supply and return line is small and the differential pressure is high. This means that if the temperature sensor on the return line is placed before or after the control valve will make a difference when measuring the energy. For example, a temperature difference of 3 K and a pressure drop of 5 bars over the control valve results in 3.4% difference in temperature before and after the control valve. 6

INNEHÅLL 1 INLEDNING 8 2 UPPDRAG 9 3 PROVBESKRIVNING 10 3.1 REDOVISAD MÄTOSÄKERHET 11 4 PROVRESULTAT 12 5 DISKUSSION 14 5.1 MÄTOSÄKERHET FÖR TEMPERATUR 14 5.2 RÄKNEEXEMPEL PÅ HUR TEMPERATURGIVAR- PLACERING PÅVERKAR KOSTNADEN 15 6 SLUTSATS 16 7 REFERENSER 17 7

1 INLEDNING Energi byter form när vatten flödar genom en styrventil. Den energi som frigörs när trycket faller över styrventilen omvandlas till värme. SP fick en förfrågan av Svensk fjärrvärmes mätargrupp i början av 2012 att ansöka till Fjärrsyn för att undersöka ett teoretiskt samband kring tryckfallets påverkan på energimätning. Teoretiska uträkningar visar att energin som omvandlas vid tryckfall över styrventiler inte är försumbar om man tittar på fjärrkylalösningar. Den registrerade energimängden kan skilja 3,4 % beroende på var man mäter temperaturen, före eller efter styrventilen. Detta i ett fall med en fjärrkylcentral, med en temperaturdifferens på 3 K och ~5 bars tryckfall över styrventilen (Frank). 8

2 UPPDRAG Uppdraget grundar sig i en rapport från Bo Frank, Heat meter error caused by pressure (Frank). Figur 1 visar på olika sätt att mäta temperaturskillnaden när styrventilen sitter på returen. Figur 1. Skiss från Bo Franks rapport som visar ett exempel där det är viktigt med temperaturgivarplacering. För att verifiera detta teoretiska samband ska temperaturen mätas före och efter en strypning. Temperaturskillnaden motsvarar då det systematiska felet för energimätaren när hänsyn inte tas till tryckskillnad. Temperaturmätningen efter strypningen motsvarar den returtemperatur som värmemätaren registrerar efter fjärrvärmecentralen och temperaturmätningen före strypningen den returtemperatur som skulle fås om differenstrycket var noll. 9

3 PROVBESKRIVNING För att undersöka tryckfallets påverkan på energimätning mäts hur temperaturen förändras efter tryckminskning, enligt Figur 2. Schematisk bild av testrigg. Temperaturskillnaden mellan T 1 och T 2 motsvarar det systematiska felet för energimätaren när hänsyn inte tas till tryckskillnad. T 2 motsvarar den returtemperatur som värmemätaren registrerar efter fjärrvärmecentralen och T 1 den returtemperatur som skulle fås om differenstrycket dp var noll. Figur 2. Schematisk bild av testrigg. En STAD-ventil kopplades ihop med två stycken mätrör med tryckuttag, både ventilen och mätrören med en invändig diameter på 25 mm. Tre temperaturgivare monterades före och efter testriggen i anslutningarna mellan testriggen och vattenförsörjningssystemet. Se Figur 3. Verklig bild av testrigg. Figur 3. Verklig bild av testrigg. För att minska mätfel på grund av eventuell skiktning monterades tre temperaturgivare i varje mätpunkt. Se Figur 4. Montering av temperaturgivare.. Medelvärdet av de tre uppmätta temperaturerna användes för att beräkna temperaturskillnaden. 10

Figur 4. Montering av temperaturgivare. Mätningarna gjordes vid två olika temperaturnivåer: rumstemperatur och 10 C. Vid mätningarna med tiogradigt vatten var testriggen isolerad för att temperaturmätningen inte skulle påverkas av omgivningstemperaturen. Se Figur 5. Testrigg, isolerad inför mätning med tiogradigt vatten. Figur 5. Testrigg, isolerad inför mätning med tiogradigt vatten. Mätning av temperaturskillnad före och efter injusteringsventilen gjordes vid differenstryck nära noll (med fullt öppen injusteringsventil) och vid differenstrycken 2, 4 och 8 bar. Flödet hölls konstant vid samtliga mätningar och valdes till 1,5 m 3 /h. 3.1 Redovisad mätosäkerhet Mätosäkerheten har uppskattats till bättre än följande värden. Differenstryck ±1 kpa Temperatur ±0,03 C Flöde ±1,5% 11

4 PROVRESULTAT Temperaturskillnaden mättes upp vid fyra olika tryckfall och vid två olika temperaturer. Den ena temperaturnivån valdes för att temperaturförlusterna mot omgivningen skulle bli så små som möjligt (rumstemperatur) och den andra temperaturnivån skulle motsvara en typisk temperaturnivå i ett fjärrkylasystem (10 C). För att minska mätosäkerheten mättes temperaturen med totalt sex temperaturgivare, tre i varje ända av testriggen. Medelvärdet av de två uppsättningarnas mätresultat gav temperaturerna T 1 och T 2. Mätresultaten redovisas i Tabell 3, Tabell 4 och i Figur 6. Tabell 3. Mätvärden vid rumstemperatur. ΔP (bar) Flöde (m³/h) T1 ( C) T2 ( C) Uppmätt ΔT Beräknat ΔT 0,0 1,51 20,67 20,64-0,02 0,00 2,0 1,50 21,12 21,17 0,05 0,04 4,0 1,50 21,69 21,75 0,07 0,08 8,0 1,50 24,14 24,31 0,17 0,16 Tabell 4. Mätvärden vid 10 C. ΔP (bar) Flöde (m³/h) T 1 ( C) T 2 ( C) Uppmätt ΔT Beräknat ΔT 0,0 1,50 10,07 10,05-0,02 0,00 2,0 1,50 10,15 10,18 0,03 0,04 4,0 1,49 10,18 10,25 0,07 0,08 8,0 1,51 10,64 10,80 0,16 0,16 Mätresultaten visar att de uppmätta temperaturdifferenserna vid tryckfall stämmer väl överens med de beräknade. Skillnaden mellan de uppmätta och beräknade värdena är som mest 0,02 K, men detta inträffar vid 0 bars differenstryck och beror troligtvis på mätfel då den uppmätta temperaturdifferensen blir negativ. Mätresultaten visar också att temperaturnivån på vattnet inte har någon påverkan på hur stor temperaturökningen vid tryckfall blir. 12

Figur 6. Grafisk beskrivning av mätresultat. 13

5 DISKUSSION 5.1 Mätosäkerhet för temperatur För att mätresultaten i projektet skulle vara tillförlitliga krävdes en hög mätnoggrannhet eftersom temperaturskillnaden beräknades vara ett fåtal hundradels grader. Vid de flesta vattentemperaturmätningar garanterar SP en mätosäkerhet på ±0,10 C för absolut temperatur. För att minska mätosäkerheten gjordes flera åtgärder: 1. Tre temperaturgivare monterades i varje mätpunkt istället för en. 2. Mätosäkerheten beräknades på temperaturskillnaden istället för på absolut temperatur. Då elimineras vissa systematiska fel. 3. En kalibrering av temperaturgivarna gjordes direkt före och direkt efter mätningarna. Detta främst för att eliminera mätosäkerhetsbidraget för långtidsstabilitet. Med dessa åtgärder bedömdes mätosäkerheten till ±0,03 C. Å ena sidan kan det konstateras att skillnaden mellan beräknad och uppmätt temperaturskillnad är mindre än mätosäkerheten i alla åtta provpunkter. Å andra sidan är mätosäkerheten fortfarande en stor del av det totala mätvärdet. 14

5.2 Räkneexempel på hur temperaturgivarplacering påverkar kostnaden I ett fjärrkylasystem kan skillnaden i temperatur mellan fram- och returledningen vara så liten att temperaturökningen vid tryckfall kan påverka energimätningen så mycket att det inte är försumbart. Exempelvis kan en temperaturdifferens på 3 K och 5 bars tryckfall över styrventilen innebära att det blir 3,4 % temperaturskillnad om man mäter temperaturen före eller efter styrventilen. För att illustrera mätresultaten kan det underlätta med ett räkneexempel: Ett kontorshus i Göteborg använde under ett år 632 MWh fjärrkyla då returtemperaturen mättes efter styrventilen. Om vi antar att fjärrkylan i Göteborg det året kostade i genomsnitt 25 öre/kwh gav det en årskostnad på 158 000 kr. Hade fjärrkylacentralens värmemätare mätt temperaturen före styrventilen hade man istället fått fram att huset använt 611 MWh fjärrkyla. Det skulle ge en årskostnad på 152 750 kr, alltså en besparing för fastighetsägaren på 5250 kr. Figur 7. Illustration av räkneexempel. 15

6 SLUTSATS De teoretiska beräkningarna gjorda av Bo Frank (Frank) stämmer väl överens med de uppmätta värdena i detta projekt. All den energi som omvandlas när trycket faller över en styrventil värmer vattnet. Detta innebär att det blir viktigt var retursidans temperaturgivare placeras i system där temperaturskillnaderna mellan framledning och retur är små och differenstrycken är höga, exempelvis i fjärrkylasystem. I ett fjärrkylasystem kan skillnaden i temperatur mellan fram- och returledningen vara så liten att temperaturökningen vid tryckfall kan påverka energimätningen så mycket att det inte är försumbart. Exempelvis kan en temperaturdifferens på 3 K och 5 bars tryckfall över styrventilen innebära att det blir 3,4 % temperaturskillnad om man mäter temperaturen före eller efter styrventilen. 16

7 REFERENSER Frank, B. (u.d.). Heat meter error caused by pressure. Hämtat från http://www.bofcon.se/doc/hm_pressure.pdf (läst 2013-05-21) 17

Forskning som stärker fjärrvärme och fjärrkyla, uppmuntrar konkurrenskraftig affärs- och teknikutveckling och skapar resurseffektiva lösningar för framtidens hållbara energisystem. Kunskap från Fjärrsyn är till nytta för fjärrvärmebranschen, kunderna, miljön och samhället i stort. Programmet finansieras av Energi myndigheten tillsammans med fjärrvärmebranschen och omsätter cirka 19 miljoner kronor om året. Mer information finns på www.fjarrsyn.se tryckfallets påverkan vid energimätning Här blir det tydligt att de teoretiska beräkningar som tidigare gjorts stämmer väl överens med de uppmätta värden som detta projekt fått fram genom mätningar i praktiken. All den energi som omvandlas när trycket faller över en styrventil värmer vattnet. Det innebär att det är viktigt var retursidans temperaturgivare placeras i system där temperaturskillnaderna mellan framledning och retur är små och differenstrycken är höga. Detta gäller till exempel i stora fjärrkylesystem. I den typen av system kan skillnaden i temperatur mellan fram- och returledningen vara så liten att temperaturökningen vid tryckfall kan påverka energimätningen så mycket att det märks. Exempelvis kan en temperaturdifferens på 3 K och 5 bars tryckfall över styrventilen innebära att det blir en skillnad i temperatur på 3,4 procent om man mäter temperaturen före eller efter styrventilen. Rapporten beskriver hur provet är gjort, vad resultaten visar och vad det betyder i praktiken. Det här utgör viktiga resultat som Svensk Fjärrvärme kommer att ta hänsyn till när de tekniska bestämmelserna uppdateras. Svensk Fjärrvärme 101 53 Stockholm Telefon 08-677 25 50 Fax 08-677 25 55 Besöksadress: Olof Palmes gata 31, 6 tr. E-post fjarrsyn@svenskfjarrvarme.se www.fjarrsyn.se