INSTALLATION INSTRUCTIONS

Relevanta dokument
INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

BBT057/ BBC057 BBCD057/ BBT057-NL HOLDEN COLORADO 9/2016+ HOLDEN TRAILBLAZER WD & 4WD Models

BBT042/ BBC042/ BBCD042 NISSAN NAVARA D40 V STX & PATHFINDER R WD & 4WD Models

Installation Instructions

INSTALLATION INSTRUCTIONS

BBT014/ BBC014/ BBCD014 PJ & PK FORD RANGER WD & 4WD Models


81152 TRANSFER CASE SHIFT HANDLE

Installation Instructions

BBT034/ BBC034/ BBCD034 VOLKSWAGEN AMAROK. Ironman 4x4 BBT/ BBC/ BBCD034 Bull Bars fit to a Volkswagen Amarok. It will take about 3 hours to install.

INSTALLATION INSTRUCTIONS

IMPORTANT! RETAIN FOR FUTURE REFERENCE PLEASE READ CAREFULLY VIKTIGT! BEHÅLL FÖR FRAMTIDA REFERENS LÄS IGENOM INSTRUKTIONSMANUALEN

SAFETY PRECAUTIONS SPECIFICATIONS

INSTALLATION INSTRUCTIONS

IMPORTANT! RETAIN FOR FUTURE REFERENCE PLEASE READ CAREFULLY VIKTIGT! BEHÅLL FÖR FRAMTIDA REFERENSLÄS IGENOM INSTRUKTIONSMANUALEN NOGGRANT

BBT034/ BBC034/ BBCD034 BBCD060/ BBT060-NL/ BB060-TL/ BB060-SL VOLKSWAGEN AMAROK

SVENSK STANDARD SS-ISO :2010/Amd 1:2010

TREX TRANSCEND RAILING

Diskant Yta eller Vikelfäste montering Mount

VASSVIK FIXED STAND SE / ENG

säkerhetsutrustning / SAFETY EQUIPMENT

Viktig information för transmittrar med option /A1 Gold-Plated Diaphragm

Support Manual HoistLocatel Electronic Locks

Industri-Vågar WEIGHING TENSIOMETER MODEL WT12 SERVICE ELLER KALIBRERING RING

Boiler with heatpump / Värmepumpsberedare

ASSEMBLY INSTRUCTIONS SCALE - SYSTEM

SAFETY PRECAUTIONS SPECIFICATIONS

Joki Joki Air. JCD70-xx JAD90-xx. lasiesta.com. Manual. Betriebsanleitung. Manuel. Manual. Manuale. Gebruiksaanwijzing.

Bathtub Filler CN EN. TBP02201 Type / TBP02202 Type. Installation Manual. Continued on the back cover

CompactAIR Center Ventilation - Filtrering - Uppvärmning CompactAIR Center Ventilation - Filtration - Heating

BBT025/ BBC025/ BBCD025 TOYOTA LANDCRUISER 200 SERIES

ASSEMBLY INSTRUCTIONS SCALE SQUARE - STANDARD

BRIC MODELL A

P650 - Takscreen. Installationsguide EN

TEXTURED EASY LOCK BLOCK INSTALLATION GUIDE. australianpaving.com.au

Monteringsanvisning Nödutrymningsbeslag ASSA 179E

LINC MODELL 13. INR SVERIGE AB Kosterögatan 15 SE Malmö 13 EN 1428:2005+A1:2008

Monteringsanvisning Podie T 4100 K

FORTA M315. Installation. 218 mm.

Beijer Electronics AB 2000, MA00336A,

BBP064/ BBT064/ BBT064-NL TOYOTA PRADO 12/2017+ Ironman 4x4 BBP/ BBT Bull Bars fit to a Toyota Prado 12/2017+ It will take about 4 hours to install.

Windlass Control Panel v1.0.1

ARC 32. Tvättställsblandare/Basin Mixer. inr.se

Företagsnamn: Grundfos Skapad av: Magnus Johansson Tel: +46(0) Datum:


Bruksanvisning Directions for use

Ringmaster RM3 - RM 5 RM3 RM 4 RM 5

Accepterad monteringsanvisning 2016:1. Metris (RSK: ) Metris S (RSK: ) Metris (RSK: )

Dokumentnamn Order and safety regulations for Hässleholms Kretsloppscenter. Godkänd/ansvarig Gunilla Holmberg. Kretsloppscenter

INKOPPLINGSANVISNING ELTRYCKSLÅS WIRING DIAGRAM SOLENOID LOCK

Montageanvisning Airway system 1000/1500 Assembly instruction Airway system 1000/1500

Plain A262. För T16 (T5) lysrör. Innehåll. Monteringsanvisning. A. Instruktion för rampmontering

Digital Personvåg MANUAL H

Installation. Twice Nisch. Twice Corner SVENSKA ENGLISH

ASSEMBLY INSTRUCTIONS SCALE CIRCLE - STANDARD

INSTALLATION INSTRUCTIONS

Contents / Innehållsförteckning

Accepterad monteringsanvisning 2016:1

Rev No. Magnetic gripper 3

INSTALLATION INSTRUCTIONS

Technical description with installation and maintenance instructions

FLUID SOLUTIONS 700ZDT & 700NDT. NAMUR Solenoid Valve 3/2 5/2 INSTALLATION, OPERATION & MAINTENANCE MANUAL. JWB USA, Inc. TUNING FLUID SOLUTIONS

Monteringsanvisning Installation instructions

VASSVIK ROCKING STAND

SAFETY PRECAUTIONS SPECIFICATIONS


IRAB Mottagare sida 2-5 Tele Radio AB Mottagare sida 6

SAFETY PRECAUTIONS SPECIFICATIONS

Installation Instructions

Accepterad monteringsanvisning 2016:1. Talis S (RSK: ) Talis S (RSK: ) 1 (12)

Accepterad monteringsanvisning 2016:1. Talis S (RSK: ) Talis S 100 CoolStart (RSK: )

Preschool Kindergarten

WALK-IN INSTALLATION INSTRUCTIONS

Styrteknik: Binära tal, talsystem och koder D3:1

LINC Modell A

DAMPER EQAZ-12, EQAZ-13, STAZ-30, STBZ-30

FD50H SLIDING DOOR SYSTEM Installation Manual

1850 x mm Clip Lock, Raised Shower Tray Kit

22200 REMOTE DIPSTICK

Installation Instructions

Nathi Skötbord Changing unit Table à langer murale Wickeltisch Verschoontafel Puslebord Cambiador de pared Přebalovací pult Fasciatoio

Accepterad monteringsanvisning 2016:1. Ecos M CoolStart (RSK: ) Ecos L CoolStart (RSK: ) 1 (12)

Instruction Manual. Svenska, English. Power Bank. Model: PRBN

MCP-16RC, Air Purification

Your No. 1 Workout. MANUAL pro

BATH MIXER 160 LINC 21. incl. HAND SHOWER. inr.se

Accepterad monteringsanvisning 2016:1. Focus (RSK: ) 1 (12)

LX Wall Mount Keyboard Arm

LÄNKHJUL S3. Monteringsanvisning för: Länkhjul S3

VARIOBARRIER S/M MIMSAFE BY CHOICE

STANDARD. UTM Ingegerd Annergren UTMS Lina Orbéus. UTMD Anders Johansson UTMS Jan Sandberg

Monteringsanvisning benfundament TM 8055, TM 8060, T 8118 K. Art nr ,

Multifunktions-Detector Multi detector

Installation Instructions

Accepterad monteringsanvisning 2016:1. Focus (RSK: ) Focus 100 CoolStart (RSK: ) (RSK: )

ES5500 PORTABLE GENERATOR

Transkript:

2010 Lennox Industries Inc. Dallas, Texas, USA INSTALLATION INSTRUCTIONS XP14 Elite Series Units HEAT PUMP UNITS 505,244M 03/10 Supersedes 10/09 Litho U.S.A. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE WARNING Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property. Installation and service must be performed by a qualified installer or service agency. CAUTION Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working near these areas during installation or while servicing this equipment. The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HFCs, and HCFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance. This unit must be matched with an indoor coil as specified in Lennox Engineering Handbook. Coils previously charged with HCFC 22 must be flushed. Table of Contents XP14 Outdoor Unit............................ 1 Shipping and Packing List...................... 1 Unit Dimensions and Parts Arrangement......... 2 General Information........................... 3 Setting the Unit............................... 3 Removing Panels............................. 5 Electrical..................................... 6 Refrigerant Piping............................. 8 Flushing Existing Line Set and Indoor Coil........ 10 Refrigerant Metering Device.................... 11 Manifold Gauge Set........................... 12 Service Valves................................ 12 Leak Testing.................................. 13 Evacuation................................... 13 Start Up...................................... 14 Refrigerant Charge............................ 14 Check Indoor Airflow before Charging............ 14 Setup for Checking and Adding Charge.......... 15 Weigh in Charge.............................. 15 Subcooling Charge............................ 15 Defrost System............................... 19 Maintenance.................................. 24 User Information.............................. 24 Start-up and Performance Checklist.............. 26 XP14 Outdoor Unit The XP14 outdoor unit uses HFC 410A HFC refrigerant. This unit must be installed with a matching indoor blower coil and line set as outlined in the Lennox Engineering Handbook. Elite Series XP14 outdoor units are designed for use in check expansion valve (CTXV) systems only and are not to be used with other refrigerant flow control devices. An expansion valve approved for use with HFC 410A must be ordered separately and installed prior to operating the unit. Shipping and Packing List 1 Assembled XP14 outdoor unit Check the unit components for shipping damage. If you find any damage, immediately contact the last carrier. 03/10 505,244M Page 1

Unit Dimensions Inches (mm) and Parts Arrangement RUN CAPACITOR DEFROST BOARD OUTDOOR FAN CONTACTOR COMPRESSOR SUCTION LINE CONNECTION REVERSING VALVE HIGH PRESSURE SWITCH TOP VIEW C LIQUID LINE CONNECTION FILTER DRIER/ LIQUID LINE CONNECTIONS PARTS ARRANGEMENT VAPOR LINE VAPOR VALVE AND GAUGE PORT/SUCTION LINE CONNECTIONS DISCHARGE AIR B LIQUID LINE CONNECTION ELECTRICAL INLETS A VAPOR LINE CONNECTION 2 (51) 4 1/4( 108) 4 3/4 (121) SIDE VIEW 1 (25) SIDE VIEW UNIT SUPPORT FEET UNIT SUPPORT FEET 8 1/2 (216) 9 1/2 (241) 16 7/8 (429) 26 7/8 (683) 8 3/4 (222) 8 1/4 (210) 8 3/4 (222) 3 3/4 (95) 5 1/2 (140) 13 1/2 (343) XP14 018 TO 030 BASE SECTION 3 1/8 (79) 30 3/4 (781) XP14 036 TO 060 BASE WITH ELONGATED LEGS 4 5/8 (117) Model No. A B C XP14 018 31 (787) 27 (686) 28 (711) XP14 024 31 (787) 27 (686) 28 (711) XP14 030 35 (889) 27 (686) 28 (711) XP14 036 31 (787) 35 1/2 (902) 39 1/2 (1003) XP14 042 39 (991) 35 1/2 (902) 39 1/2 (1003) XP14 048 39 (991) 35 1/2 (902) 39 1/2 (1003) XP14 060 45 (1143) 35 1/2 (902) 39 1/2 (1003) 505244M 10/09 Page 2

WARNING Product contains fiberglass wool. Disturbing the insulation of this product during installation, maintenance, or repair will expose you to fiberglass wool. Breathing this may cause lung cancer. (Fiberglass wool is know to the State of California to cause cancer.) Fiberglass wool may also cause respiratory, skin and eye irritation. To reduce exposure to this substance or for further information, consult material safety data sheets available from address show below, or contact your supervisor. Lennox Industries Inc., PO Box 79011, Dallas, TX 75379 9011 General Information These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation. When servicing or repairing HVAC components, ensure the fasteners are appropriately tightened. Table 1 shows torque values for fasteners. Table 1. Torque Requirements Part Recommended Torque Service valve cap 8 ft. lb. 11 NM Sheet metal screws 16 in. lb. 2 NM Machine screws #8 16 in. lb. 2 NM Compressor bolts 90 in. lb. 10 NM Gauge port seal cap 8 ft. lb. 11 NM 4. Locate the unit so prevailing winter winds will not blow into the coil. 5. Locate unit away from overhanging roof lines which would allow water or ice to drop on, or in front of, coil or into unit. ÍÍÍÍÍÍÍÍÍÍÍÍÍÍ ÍÍÍÍÍÍÍÍÍÍÍÍÍÍ See NOTES ÍÍÍÍÍÍÍÍÍÍÍÍÍÍ ÍÍÍÍÍÍÍÍÍÍÍÍÍÍ ÍÍÍÍÍÍÍÍÍÍÍÍÍÍ ÍÍÍÍÍÍÍÍÍÍÍÍÍÍ See See ÍÍÍÍÍÍÍÍÍÍÍÍÍÍ NOTES NOTES ÍÍÍÍÍÍÍÍÍÍÍÍÍÍ ÍÍÍÍÍÍÍÍÍÍÍÍÍÍ ÍÍÍÍÍÍÍÍÍÍÍÍÍÍ Control See NOTES Box ÍÍÍÍÍÍÍÍÍÍÍÍÍÍ NOTES: Service clearance of 30 in. (762 mm) must be maintained on one of the sides adjacent to the control box. Clearance to one of the other three sides must be 36 in. (914 mm) Clearance to one of the remaining two sides may be 12 in. (305 mm) and the final side may be 6 in. (152 mm). A clearance of 24 in. (610 mm) must be maintained between two units. 48 in. (1219 mm) clearance required on top of unit. Setting the Unit CAUTION In order to avoid injury, take proper precaution when lifting heavy objects. Outdoor units operate under a wide range of weather conditions; therefore, several factors must be considered when positioning the outdoor unit. Position the unit to allow adequate airflow and servicing clearance. Maintain a minimum clearance of 24 inches (610 mm) between multiple units as illustrated in figure 1 for installation clearances. 1. Place a sound-absorbing material, such as Isomode, under the unit if it will be installed in a location or position that will transmit sound or vibration to the living area or adjacent buildings. 2. Install the unit high enough above ground or roof to allow adequate drainage of defrost water and prevent ice build-up. 3. In heavy snow areas, do not locate unit the where snowdrifts will likely build. The unit base should be elevated above the depth of average snows. NOTE - Elevation of the unit may be accomplished by constructing a frame using suitable materials. If a support frame is constructed, it must not block drain holes in unit base. Page 3 Figure 1. Installation Clearances SLAB MOUNTING When installing unit at grade level, the top of the slab should be high enough above grade so that water from higher ground will not collect around the unit. The slab should have a slope tolerance away from the building of 2 degrees or 2 inches per 5 feet (50 mm per 1500 mm) to prevent ice build-up under the unit during a defrost cycle. NOTE If necessary for stability, anchor unit to slab as described in Stabilizing Unit on Uneven Surfaces on page 4. INSTALL UNIT LEVEL OR, IF ON A SLOPE, MAINTAIN SLOPE TOLERANCE OF 2 DEGREES (OR 2 INCHES PER 5 FEET [50 MM PER 1.5 M]) AWAY FROM BUILDING STRUCTURE. GROUND LEVEL BUILDING STRUCTURE MOUNTING SLAB Figure 2. Slab Mounting Options XP14 SERIES

ELEVATING THE UNIT (SMALL BASE UNITS) If additional elevation is necessary, raise the unit by extending the length of the unit support feet. This may be done by cutting four equal true cut lengths of Schedule (SCH) 40, 4" (101.6mm) piping to the height required as illustrated in figure 3. NOTE Keep the height of extenders short enough to ensure a sturdy installation. If it is necessary to extend further, consider a different type of field fabricated framework that is sturdy enough for greater heights. The inside diameter of the 4" (101.6mm) piping is approximately 0.25" (6.35mm) greater than the pre installed feet on the unit. Devise a shim that will take up the space and hold the extenders onto the feet during this procedure. Small strips of 0.125" (3.175mm) thick adhesive foam may be used. One or two small 1" (25.4mm) square strips should be adequate to hold the extender in place. Base NOTE Keep the height of extenders short enough to ensure a sturdy installation. If it is necessary to extend further, consider a different type of field fabricated framework that is sturdy enough for greater heights. Leg Detail Base 2" (50.8mm) SCH 40 Female Threaded Adapter Figure 4. Elevated Slab Mounting using Feet Extenders (Larger Base Units) STABILIZING UNIT ON UNEVEN SURFACES To help stabilize an outdoor unit, some installations may require strapping the unit to the pad using brackets and anchors commonly available in the marketplace. Leg Detail 4" (101.6mm) SCH 40 Piping TYPICAL INSTALLATION WITH 3 TO 4 IN. EXTENDERS INSTALLED! ALWAYS USE STABILIZER BRACKET ON ELEVATED INSTALLATIONS BUILDING STRUCTURE MOUNTING SLAB Figure 3. Elevated Slab Mounting using Feet Extenders (Small Base Units) ELEVATING THE UNIT (LARGER BASE UNITS) Unlike the small base units which use round feet, the larger base units are outfitted with elongated feet as illustrated in figure 4. which uses a similar method for elevating the unit height. If additional elevation is necessary, raise the unit by extending the length of the unit support feet. This may be done with 2" SCH 40 female threaded adapter. The specified coupling will fit snuggly into the recess portion of the feet. Use additional 2" SCH 40 male threaded adaptors which can be threaded into the female threaded adaptors to make additional adjustments to the level of the unit. STABILIZER BRACKETS GROUND LEVEL Figure 5. Elevated Slab Mounting using Feet Extenders Unit Stabilizer Bracket Use (field provided): Always use stabilizers when unit is raised above the factory height. (Elevated units could become unstable in gusty wind conditions). Stabilizers may be used on factory height units when mounted on unstable or uneven surface. 505244M 10/09 Page 4

With unit positioned at installation site, remove two side louvered panels to expose the unit base pan. Install the brackets as illustrated in figure 6 using conventional practices; replace the panels after installation is complete. #10 1/2" LONG SELF DRILLING SHEET METAL SCREWS STABILIZING BRACKET (18 GAUGE METAL 2" WIDTH; HEIGHT AS REQ D) #10 1 1/4" LONG HEX HD SCREW & FLATWASHER PLASTIC ANCHOR USE IF CONCRETE (HOLE DRILL 1/4"); NOT IF PLASTIC SLAB (HOLE DRILL 1/8"). Deck Top Mounting STABILIZING BRACKET (18 GAUGE METAL 2" WIDTH; HEIGHT AS REQ D); BEND TO FORM RIGHT ANGLE MINIMUM 1 PER SIDE FOR EXTRA STABILITY COIL ONE BRACKET PER SIDE (MIN.); FOR EXTRA STABILITY, 2 BRACKETS PER SIDE, 2" FROM EACH CORNER. BASE PAN CORNER POST Figure 6. Installing Stabilizer Brackets (Slab Side Mounting) ROOF MOUNTING Install unit 6" (152 mm) above the roof surface to avoid ice build up around the unit. Locate the unit above a load bearing wall or area of the roof that can adequately support the unit. Consult local codes for rooftop applications. If unit cannot be located away from prevailing winter winds, construct a wind barrier sized at least the same height and width as outdoor unit. Position barrier 24" (610 mm) from the sides of the unit in direction of prevailing winds as illustrated in figure 7. prevailing winter winds Removing Panels Remove the louvered panels as follows: 1. Remove two screws, allowing the panel to swing open slightly as illustrated in figure 8. 2. Hold the panel firmly throughout this procedure. Rotate bottom corner of panel away from hinge corner post until lower three tabs clear the slots as illustrated figure 8, Detail B. 3. Move panel down until lip of upper tab clears the top slot in corner post as illustrated in figure 8, Detail A. Position and Install PanelPosition the panel almost parallel with the unit as illustrated in figure 9, Detail D on page 6 with the screw side as close to the unit as possible. Then, in a continuous motion: slightly rotate and guide the lip of top tab inward as illustrated in figure 8, Details A and C; then upward into the top slot of the hinge corner post. rotate panel to vertical to fully engage all tabs. holding the panel s hinged side firmly in place, close the right hand side of the panel, aligning the screw holes. When panel is correctly positioned and aligned, insert the screws and tighten.! Do not allow panels to hang on unit by top tab. Tab is for alignment and not designed to support weight of panel. Panel shown slightly rotated to allow top tab to exit (or enter) top slot for removing (or installing) panel. LIP Detail A Detail B SCREW HOLES wind barrier inlet air 24" (610 mm) inlet air inlet air ROTATE IN THIS DIRECTION; THEN DOWN TO REMOVE PANEL Detail C inlet air Figure 7. Rooftop Application with Wind Barrier Figure 8. Removing/Installing Louvered Panels (Details A, B and C) Page 5 XP14 SERIES

MAINTAIN MINIMUM PANEL ANGLE (AS CLOSE TO PARALLEL WITH THE UNIT AS POSSIBLE) WHILE INSTALLING PANEL. HOLD DOOR FIRMLY TO THE HINGED ANGLE MAY BE TOO SIDE TO MAINTAIN EXTREME FULLY ENGAGED TABS 4. Units are approved for use only with copper conductors. (A complete unit wiring diagram is located inside the unit control box cover.) PREFERRED ANGLE FOR INSTALLATION Detail D Figure 9. Removing/Installing Louvered Panels (Detail D) CAUTION To prevent personal injury, or damage to panels, unit or structure, be sure to observe the following: While installing or servicing this unit, carefully stow all removed panels out of the way, so that the panels will not cause injury to personnel, nor cause damage to objects or structures nearby, nor will the panels be subjected to damage (e.g., being bent or scratched). While handling or stowing the panels, consider any weather conditions, especially windy conditions, that may cause panels to be blown around and battered. Electrical In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC). Refer to the furnace or blower coil installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size. 1. Install line voltage power supply to unit from a properly sized unit disconnect switch. 2. Ground the unit at the unit disconnect switch or to earth ground. 3. To facilitate conduit, a hole is provided in the bottom of the control box. Connect conduit to the control box using a proper conduit fitting. WARNING! ELECTRIC SHOCK HAZARD. Can cause INJU- RY or DEATH. Unit must be grounded in accordance with national and local codes. NOTE For use with copper conductors only. Refer to unit rating plate for minimum circuit ampacity and maximum overcurrent protection size. Figure 10. Outdoor Unit Typical Field Wiring NOTE For proper voltages, select thermostat wire gauge per the following chart: Table 2. Wire Run Lengths Wire run length AWG # Insulation type less than 100 (30m) 18 color coded, temperature more than 100 (30m) 16 rating 35 º C minimum 5. Install room thermostat (ordered separately) on an inside wall approximately in the center of the conditioned area and 5 feet (1.5 m) from the floor. It should not be installed on an outside wall or where it can be affected by sunlight, drafts or vibrations. 6. Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit. See figures 11 and 12 on page 7. NOTE 24V, Class II circuit connections are made in the low voltage junction box.) WARNING Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and local codes. Line voltage is present at all components when unit is not in operation on units with single-pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies. 505244M 10/09 Page 6

Thermostat Indoor Unit Outdoor Unit R C W1 G O Y1 24V power common 1st-stage auxiliary heat indoor blower reversing valve compressor R C W1 W2 W3 G 24V power common 1st-stage auxiliary heat (SOME CONNECTIONS MAY NOT APPLY. REFER TO SPECIFIC THERMOSTAT AND INDOOR UNIT.) Figure 11. Outdoor Unit and Blower Unit Thermostat Designations R C W1 O Y1 Thermostat Indoor Unit Outdoor Unit R C E W1 G O Y1 24V power common emergency heat 1st-stage auxiliary heat indoor blower reversing valve compressor R C W1 W2 W3 G 24V power common 1st-stage auxiliary heat (SOME CONNECTIONS MAY NOT APPLY. REFER TO SPECIFIC THERMOSTAT AND INDOOR UNIT.) R C W1 O Y1 EMERGENCY HEAT RELAY OUTDOOR THERMOSTAT Figure 12. Outdoor Unit and Blower Unit Thermostat Designations (with Emergency Heat Relay) Figure 13. Typical XP14 Wiring Page 7 XP14 SERIES

Refrigerant Piping The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFC s, HFC s, and HCFC s) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance. If the XP14 unit is being installed with a new indoor coil and line set, the plumbing connections should be made as outlined in this section. If an existing line set and/or indoor coil is going to be used to complete the XP14 system, refer to the following section that includes flushing procedures. Field refrigerant piping consists of liquid and vapor lines from the outdoor unit (sweat connections) to the indoor coil (flare or sweat connections). Use Lennox L15 (sweat, non-flare) series line sets as shown in table 3 or use field-fabricated refrigerant lines. Refer to Refrigerant Piping Guide (Corp. 9351 L9) for proper size, type, and application of field fabricated lines. Valve sizes are also listed in table 3. REFRIGERANT LINE CONNECTIONS XP14 OUTDOOR UNIT MATCHED WITH NEW INDOOR COIL AND LINE SET If replacing an existing coil equipped with a liquid line functioning as a metering orifice, replace the liquid line prior to installing the XP14 unit. Line sets are described in table 3. Table 3. Refrigerant Line Sets Model 018 024 030 036 042 048 060 Valve Field Connections Liquid Line 3/8 in. (10 mm) 3/8 in. (10 mm) 3/8 in. (10 mm) Vapor Line 3/4 in (19 mm) 7/8 in (22 mm) 1 1/8 in. (29 mm) Recommended Line Set Liquid Line 3/8 in. (10 mm) 3/8 in. (10 mm) 3/8 in. (10 mm) Vapor Line 3/4 in (19 mm) 7/8 in (22 mm) 1 1/8 in. (29 mm) L15 Line Sets L15 41 15 ft. 50 ft. (4.6 m 15 m) L15 65 15 ft. 50 ft. (4.6 m 15 m) Field Fabricated NOTE When installing refrigerant lines, refer to Lennox Refrigerant Piping Guide (Corp. 9351 L9) or Lennox Technical Support Department Product Applications Group for assistance. In addition, be sure to consider the following points: Select line set diameters from table 3 to ensure that oil returns to the compressor. Units are designed for line sets of up to 50 feet (15 m); for longer line sets, consult piping guidelines. Size vertical vapor riser to maintain minimum velocity at minimum capacity. INSTALLING REFRIGERANT LINE Pay close attention to line set isolation during installation of any heat pump or a/c system. When properly isolated from building structures (walls, ceilings. floors), the refrigerant lines will not create unnecessary vibration and subsequent noises. Also, consider the following when placing and installing a high efficiency outdoor unit: 1. PlacementSome localities are adopting sound ordinances based on the unit s noise level observed from the adjacent property, not from the installation property. Install the unit as far as possible from the property line. When possible, do not install the unit directly outside a window. Glass has a very high level of sound transmission. Figure 14 shows how to place the outdoor unit and line set. Install unit away from windows Two 90 elbows installed in line set will reduce line set vibration. Figure 14. Outside Unit Placement 2. Line Set IsolationThe following illustrations demonstrate procedures which ensure proper refrigerant line set isolation. Figure 15 on page 9 shows how to install line sets on horizontal runs. Figure 16 on page 9 shows how to install line sets on vertical runs. Figure 17 on page 9 shows how to make a transition from horizontal to vertical 505244M 10/09 Page 8

TO HANG LINE SET FROM JOIST OR RAFTER, USE EITHER METAL STRAPPING MATERIAL OR ANCHORED HEAVY NYLON WIRE TIES. WIRE TIE (AROUND SUCTION LINE ONLY) ANCHORED HEAVY NYLON WIRE TIE STRAPPING MATERIAL (AROUND SUCTION LINE ONLY) 8 FEET FLOOR JOIST OR ROOF RAFTER 8 FEET TAPE OR WIRE TIE WALL STUD STRAP LIQUID LINE TO SUCTION LINE METAL SLEEVE TAPE OR WIRE TIE STRAP THE SUCTION LINE TO THE JOIST OR RAFTER AT 8 FEET INTERVALS THEN STRAP THE LIQUID LINE TO THE SUCTION LINE. METAL SLEEVE LIQUID LINE SUCTION LINE WRAPPED IN ARMAFLEX FLOOR JOIST OR ROOF RAFTER AUTOMOTIVE MUFFLER-TYPE HANGER Figure 15. Refrigerant Line Sets: Installing Horizontal Runs - REFRIGERANT LINES MUST NOT CONTACT WALL. WOOD BLOCK BETWEEN STUDS NOTE SIMILAR INSTALLATION PRACTICES SHOULD BE USED IF LINE SET IS TO BE INSTALLED ON EXTERIOR OF OUTSIDE WALL. SUCTION LINE WRAPPED WITH ARMAFLEX LIQUID LINE PVC PIPE OUTSIDE WALL OUTSIDE WALL FIBERGLASS INSULATION CAULK SLEEVE SUCTION LINE WIRE TIE STRAP SLEEVE LIQUID LINE INSIDE WALL WIRE TIE WOOD BLOCK WIRE TIE STRAP! REFRIGERANT LINES MUST NOT CONTACT STRUCTURE. Figure 16. Refrigerant Line Sets: Installing Vertical Runs (New Construction Shown) WALL STUD METAL SLEEVE STRAP LIQUID LINE TO SUCTION LINE LIQUID LINE SUCTION LINE WRAPPED IN ARMAFLEX Figure 17. Refrigerant Line Sets: Transition from Vertical to Horizontal BRAZING CONNECTION PROCEDURE WARNING Polyol ester (POE) oils used with HFC 410A refrigerant absorb moisture very quickly. It is very important that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make connections. 1. Cut ends of the refrigerant lines square (free from nicks or dents). Debur the ends. The pipe must remain round; do not pinch end of the line. 2. Flow dry nitrogen through the refrigerant piping while making line set connections; this prevents carbon deposits (oxidation) buildup on the inside of the joints being brazed. Such buildup may restrict refrigerant flow through screens and metering devices. To do this: Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the Schrader port connection on the vapor service valve and out of the Schrader port connection on the liquid service valve. (Metering device (CTXV and RFC) will allow low pressure nitrogen to flow through the system.) Page 9 XP14 SERIES

While nitrogen is flowing, braze refrigerant line set to the indoor and outdoor units. : The flow of nitrogen must have an escape path other than through the joint to be brazed. 3. Use silver alloy brazing rods (5 or 6 percent minimum silver alloy for copper to copper brazing or 45 percent silver alloy for copper to brass or copper to steel brazing) which are rated for use with HFC 410A refrigerant. 4. Wrap a wet cloth around the valve body and the copper tube stub to protect it from heat damage during brazing. Wrap another wet cloth underneath the valve body to protect the base paint. NOTE The tube end must stay bottomed in the fitting during final assembly to ensure proper seating, sealing and rigidity. 5. Install a field provided check expansion valve (approved for use with HFC 410A refrigerant) in the liquid line at the indoor coil. Flushing Existing Line Set and Indoor Coil If this unit is being matched with an approved line set or indoor coil which was previously charged with HCFC 22 refrigerant, or if it is being matched with a coil which was manufactured before January of 1999, the coil and line set must be flushed prior to installation. Take care to empty all existing traps. Polyol ester (POE) oils are used in Lennox units charged with HFC 410A refrigerant. Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the check expansion valve, reducing system performance and capacity. Failure to properly flush the system per the instructions below will void the warranty. WARNING Danger of fire. Bleeding the refrigerant charge from only the high side may result in the low side shell and suction tubing being pressurized. Application of a brazing torch while pressurized may result in ignition of the refrigerant and oil mixture check the high and low pressures before unbrazing. CAUTION This procedure should not be performed on systems which contain contaminants (Example: compressor burn out). The line set and indoor coil must be flushed with at least the same amount of clean refrigerant that previously charged the system. Check the charge in the flushing cylinder before proceeding. EQUIPMENT REQUIRED FOR FLUSHING LINE SET The following equipment is required to flush the existing line set and indoor coil: two clean HCFC 22 recovery cylinders oilless recovery machine with a pump down feature gauge set for HCFC 22 refrigerant gauge set for HFC 410A refrigerant (see Manifold Gauge Set section on page 12). FLUSHING PROCEDURE 1. Remove existing HCFC 22 refrigerant using the following, applicable procedure as illustrated in figure 18: If the existing outdoor unit is not equipped with shut off valves, or if the unit is not operational AND you plan to use the existing HCFC 22 refrigerant to flush the system Disconnect all power to the existing outdoor unit. Connect to the existing unit, a clean recovery cylinder and the recovery machine according to the instructions provided with the recovery machine. Remove all HCFC 22 refrigerant from the existing system. Check gauges after shutdown to confirm that the entire system is completely void of refrigerant. Disconnect the liquid and vapor lines from the existing outdoor unit. If the existing outdoor unit is equipped with manual shut off valves AND you plan to use NEW HCFC 22 refrigerant to flush the system Start the existing HCFC 22 system in the cooling mode and close the liquid line valve. Pump all of the existing HCFC 22 refrigerant back into the outdoor unit. (It may be necessary to bypass the low pressure switches to ensure complete refrigerant evacuation.) When the low side system pressures reach 0 psig, close the vapor line valve. Disconnect all power to the existing outdoor unit. Check gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system. Disconnect the liquid and vapor lines from the existing outdoor unit. 2. Remove the existing outdoor unit. Set the new HFC 410A unit and follow the Brazing Connection Procedure provided on page 9 to make line set connections. DO NOT install HFC 410A check/expansion valve at this time. 3. Make low voltage and line voltage connections to the new outdoor unit. DO NOT turn on power to the unit or open the outdoor unit service valves at this time. 505244M 10/09 Page 10

SUCTION LINE SERVICE VALVE EXISTING INDOOR UNIT LIQUID LINE SERVICE VALVE RECOVERY CYLINDER A B C D D SUCTION LIQUID A INVERTED HCFC 22 CYLINDER CONTAINS CLEAN HCFC 22 TO BE USED FOR FLUSHING. B NEW OUTDOOR UNIT LOW OPENED TANK RETURN GAUGE MANIFOLD INLET DISCHARGE RECOVERY MACHINE CLOSED HIGH NOTE The inverted HCFC 22 cylinder must contain at least the same amount of refrigerant as was recovered from the existing system. C Inverted HCFC 22 cylinder with clean refrigerant to the suction service valve. HCFC 22 gauge set (low side) to the liquid line valve. HCFC 22 gauge set center port to inlet on the recovery machine. with an empty recovery tank to the gauge set. Connect recovery tank to recovery machines per machine instructions. Figure 18. Flushing Connections 4. Remove the existing HCFC 22 refrigerant flow control orifice or check expansion valve before continuing with flushing procedures. HCFC 22 flow control devices (fixed orifice/check expansion valve) are not approved for use with HFC 410A refrigerant and may prevent proper flushing. Use a field provided fitting to reconnect the lines. 5. Remove the pressure tap valve cores from the XP14 unit s service valves. Connect an HCFC 22 cylinder with clean refrigerant to the vapor service valve. Connect the HCFC 22 gauge set to the liquid line valve and connect a recovery machine with an empty recovery tank to the gauge set. 6. Set the recovery machine for liquid recovery and start the recovery machine. Open the gauge set valves to allow the recovery machine to pull a vacuum on the existing system line set and indoor coil. 7. Invert the cylinder of clean HCFC 22 and open its valve to allow liquid refrigerant to flow into the system through the vapor line valve. Allow the refrigerant to pass from the cylinder and through the line set and the indoor coil before it enters the recovery machine. 8. After all of the liquid refrigerant has been recovered, switch the recovery machine to vapor recovery so that all of the HCFC 22 vapor is recovered. Allow the recovery machine to pull a vacuum on the system. NOTE A single system flush should remove all of the mineral oil from the existing refrigerant lines and indoor coil. A second flushing may be done (using clean refrigerant) if insufficient amounts of mineral oil were removed during the first flush. After each system flush, allow the recovery machine to pull a vacuum on the system at the end of the procedure. 9. Close the valve on the inverted HCFC 22 drum and the gauge set valves. Pump the remaining refrigerant out of the recovery machine and turn the machine off. 10. Use dry nitrogen to break the vacuum on the refrigerant lines and indoor coil before removing the recovery machine, gauges and HCFC 22 refrigerant drum. Reinstall pressure tap valve cores into XP14 unit s service valves. 11. Install check expansion valve (approved for use with HFC 410A refrigerant) in the liquid line at the indoor coil. Refrigerant Metering Device XP14 units may be used in check thermal expansion valve (CTXV) systems only. See indoor coil installation instructions and the Lennox engineering handbook for approved HFC 410A valve match ups and application information. NOTE HFC 410A systems will not operate properly with an HCFC 22 valve. Check thermal expansion valves equipped with fittings are available from Lennox. Refer to the Engineering Handbook for applicable expansion valves for use with specific match-ups. (Uncased Coil Shown) TWO PIECE PATCH PLATE (uncased coil only) DISTRIBUTOR TUBES ACCESS FITTING (no valve core) On smaller lines, bulb may be mounted on top 12 9 Do not mount bulb on bottom of line Suction Line Bulb ORIFICE HOUSING O RING EQUALIZER LINE SENSING BULB (insulation required) 1/2" & smaller suction line 3 5/8" & larger suction line EXPANSION VALVE (see note) STRAINER Remove and discard SEAL ASSEMBLY (if applicable) SUCTION LINE O RING SENSING LINE LIQUID LINE NOTE If necessary, remove HCFC 22 flow control device (fixed orifice/check expansion valve) from existing line set before installing HFC 410A approved expansion valve and o ring. Figure 19. Metering Device Installation Page 11 XP14 SERIES

CHECK EXPANSION VALVE BIFLOW FILTER / DRIER DISTRIBUTOR OUTDOOR COIL OUTDOOR UNIT REVERSING VALVE NOTE ARROWS INDICATE DIRECTION OF REFRIGERANT FLOW LOW PRESSURE HUGH PRESSURE MUFFLER INDOOR UNIT GAUGE MANIFOLD TO HFC 410 A DRUM LIQUID LINE SERVICE PORT COMPRESSOR VAPOR SERVICE PORT VAPOR LINE VALVE VAPOR SERVICE PORT NOTE Use gauge ports on vapor line valve and liquid valve for evacuating refrigerant lines and indoor coil. Use vapor gauge port to measure vapor pressure during charging. CHECK EXPANSION VALVE INDOOR COIL Figure 20. XP14 Cooling Cycle (Showing Gauge Manifold Connections) Failure to remove a fixed orifice when installing an expansion valve on the indoor coil will result in improper operation and damage to the system. If you install a check thermal expansion valve with an indoor coil that includes a fixed orifice, remove the orifice before the check expansion valve is installed. See figure 19 for installation of the check expansion valve. Manifold Gauge Set Manifold gauge sets used with systems charged with HFC 410A refrigerant must be capable of handling the higher system operating pressures. The gauges should be rated for use with pressures of 0 800 on the high side and a low side of 30" vacuum to 250 psi with dampened speed to 500 psi. Gauge hoses must be rated for use at up to 800 psi of pressure with a 4000 psi burst rating. Service Valves The service valves and gauge ports are used for leak testing, evacuating, charging and checking charge. Each valve is equipped with a service port which has a factory installed Schrader valve. A service port cap protects the Schrader valve from contamination and serves as the primary leak seal. To Access Schrader Port: 1. Remove service port cap with an adjustable wrench. 2. Connect gauge to the service port. 3. When testing is completed, replace service port cap. Tighten finger tight, then torque per table 1 on page 3. To Open Front-Seated Service Valves: 1. Remove stem cap with an adjustable wrench. 2. Use a service wrench with a hex head extension (3/16" for liquid-line valve sizes; 5/16" for vapor-line valve sizes) to back the stem out counterclockwise as far as it will go. 3. Replace the stem cap. Tighten finger tight, then torque per table 1 on page 3. To Close Front-Seated Service Valves: 1. Remove the stem cap with an adjustable wrench. 2. Use a service wrench with a hex head extension (3/16" for liquid-line valve sizes; 5/16" for vapor-line valve sizes) to turn the stem clockwise to seat the valve. Tighten it firmly. 3. Replace the stem cap. Tighten finger tight, then torque per table 1 on page 3. SCHRADER VALVE [OPEN TO LINE SET WHEN VALVE IS CLOSED (FRONT SEATED)] TO OUT- DOOR COIL SERVICE PORT CAP STEM CAP INSERT HEX WRENCH HERE TO INDOOR COIL (VALVE FRONT-SEATED) Valve in closed position Valve in open position Figure 21. Front-Seated Liquid Line Valve Vapor Line Ball Valve Ball-type service valves as illustrated in figure 22 function the same way as the other valves but cannot be rebuilt; if one fails, replace with a new valve. The ball valve is equipped with a service port with a factory installed Schrader valve. A service port cap protects the Schrader valve from contamination and assures a leak free seal. 505244M 10/09 Page 12

USE ADJUSTABLE WRENCH TO OPEN: ROTATE STEM COUNTER-CLOCKWISE 90. TO CLOSE: ROTATE STEM CLOCKWISE 90. TO INDOO R COIL STEM CAP STEM SERVICE PORT TO OUTDOOR COIL BALL (SHOWN CLOSED) SCHRADER VALVE SERVICE PORT CAP Figure 22. Ball Type Vapor Valve (Valve Closed) Leak Testing After the line set has been connected to the indoor and outdoor units, check the line set connections and indoor unit for leaks. WARNING Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly. WARNING Fire, Explosion and Personal Safety Hazard. Failure to follow this warning could result in damage, personal injury or death. Never use oxygen to pressurize or purge refrigeration lines. Oxygen, when exposed to a spark or open flame, can cause damage by fire and/ or an explosion, that could result in personal injury or death. WARNING Danger of explosion! When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kpa). USING AN ELECTRONIC LEAK DETECTOR Leak detector must be capable of sensing HFC refrigerant. 1. Connect a cylinder of HFC 410A to the center port of the manifold gauge set. 2. With both manifold valves closed, connect the cylinder of HFC 410A refrigerant. Open the valve on the HFC 410A cylinder (vapor only). 3. Open the high pressure side of the manifold to allow HFC 410A into the line set and indoor unit. Weigh in a trace amount of HFC 410A. [A trace amount is a maximum of 2 ounces (57 g) refrigerant or 3 pounds (31 kpa) pressure]. Close the valve on the HFC 410A cylinder and the valve on the high pressure side of the manifold gauge set. Disconnect HFC 410A cylinder. 4. Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set. 5. Connect the manifold gauge set high pressure hose to the vapor valve service port. (Normally, the high pressure hose is connected to the liquid line port; however, connecting it to the vapor port better protects the manifold gauge set from high pressure damage.) 6. Adjust dry nitrogen pressure to 150 psig (1034 kpa). Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit. 7. After a few minutes, open a refrigerant port to ensure the refrigerant you added is adequate to be detected. (Amounts of refrigerant will vary with line lengths.) Check all joints for leaks. Purge dry nitrogen and HFC 410A mixture. Correct any leaks and recheck. Evacuation Evacuating the system of noncondensables is critical for proper operation of the unit. Noncondensables are defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Noncondensables and water vapor combine with refrigerant to produce substances that corrode copper piping and compressor parts. Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument that reads from 50 microns to at least 23,000 microns. 1. Connect manifold gauge set to the service valve ports as follows: low pressure gauge to vapor line service valve high pressure gauge to liquid line service valve 2. Connect micron gauge. 3. Connect the vacuum pump (with vacuum gauge) to the center port of the manifold gauge set. 4. Open both manifold valves; start the vacuum pump. 5. Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury). During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once to determine if there is a rapid rise in absolute pressure. A rapid rise in pressure indicates a relatively large leak. If this occurs, repeat the leak testing procedure. Page 13 XP14 SERIES

NOTE The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure. 6. When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), close the manifold gauge valves, turn off the vacuum pump and disconnect the manifold gauge center port hose from vacuum pump. Attach the manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kpa) and purge the hose. Open the manifold gauge valves to break the vacuum in the line set and indoor unit. Close the manifold gauge valves. WARNING Danger of Equipment Damage! Avoid deep vacuum operation. Do not use compressors to evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty. 7. Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the dry nitrogen from the line set and indoor unit. 8. Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20 minute period after shutting off the vacuum pump and closing the manifold gauge valves. 9. When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to an upright cylinder of HFC 410A refrigerant. Open the manifold gauge valves to break the vacuum from 1 to 2 psig positive pressure in the line set and indoor unit. Close manifold gauge valves and shut off the HFC 410A cylinder and remove the manifold gauge set. Start Up If unit is equipped with crankcase heater, it should be energized 24 hours before unit start up to prevent compressor damage as a result of slugging. 1. Rotate fan to check for frozen bearings or binding. 2. Inspect all factory and field-installed wiring for loose connections. NOTE After the system has been evacuated and before completing all the remaining start up steps, this is the ideal time to adjust the amount of refrigerant made necessary by line set length difference and by the specific indoor unit match up. Skip to the paragraph Setup for Checking and Adding Charge" on page 15 to setup for charging and for determining if charge is needed; adjust the charge accordingly. 3. Open the liquid line and vapor line service valves (counterclockwise) to release refrigerant charge (contained in outdoor unit) into the system. 505244M 10/09 Page 14 4. Replace stem caps and secure finger tight, then tighten an additional (1/6) one-sixth of a turn. 5. Check voltage supply at the disconnect switch. The voltage must be within the range listed on the unit nameplate. If not, do not start the equipment until the power company has been consulted and the voltage condition has been corrected. 6. Set the thermostat for a cooling demand. Turn on power to indoor blower unit and close the outdoor unit disconnect to start the unit. 7. Recheck voltage while the unit is running. Power must be within range shown on the nameplate. Mineral oils are not compatible with HFC 410A. If oil must be added, it must be a polyol ester oil. Refrigerant Charge This system is charged with HFC 410A refrigerant which operates at much higher pressures than HCFC 22. The recommended check expansion valve is approved for use with HFC 410A. Do not replace it with a valve that is designed to be used with HCFC 22. This unit is NOT approved for use with coils that include metering orifices or capillary tubes. Units are factory-charged with the amount of HFC 410A refrigerant indicated on the unit rating plate. This charge is based on a matching indoor coil and outdoor coil with 15 ft. (4.6 m) line set. For varying lengths of line set, refer to table 3 for refrigerant charge adjustment. A blank space is provided on the unit rating plate to list the actual field charge. Check Indoor Airflow before Charging Check airflow before charging! NOTE Be sure that filters and indoor and outdoor coils are clean before testing. COOLING MODE INDOOR AIRFLOW CHECK Check airflow using the Delta T (DT) process (figure 23). HEATING MODE INDOOR AIRFLOW CHECK Blower airflow (CFM) may be calculated by energizing electric heat and measuring: temperature rise between the return air and supply air temperatures at the indoor coil blower unit, voltage supplied to the unit, amperage being drawn by the heat unit(s). Then, apply the measurements taken in following formula to determine CFM: CFM = Amps x Volts x 3.41 1.08 x Temperature rise (F) Check indoor airflow using the step procedures as illustrated in figure 23.

Temp. of air entering indoor coil ºF DRY BULB Dry bulb DT 80 24 24 24 23 23 22 22 22 20 19 18 17 16 15 78 23 23 23 22 22 21 21 20 19 18 17 16 15 14 76 22 22 22 21 21 20 19 19 18 17 16 15 14 13 74 21 21 21 20 19 19 18 17 16 16 15 14 13 12 A 72 20 20 19 18 17 17 16 15 15 14 13 12 11 10 70 19 19 18 18 17 17 16 15 15 14 13 12 11 10 Wet bulb ºF 57 58 59 60 61 62 63 64 65 66 67 68 69 70 B C 53º T Drop 19º air flow All temperatures are expressed in ºF air flow INDOOR COIL B 64º WET BULB A 72º DRY BULB Step 1. Determine the desired DTMeasure entering air temperature using dry bulb (A) and wet bulb (B). DT is the intersecting value of A and B in the table (see triangle). Step 2. Find temperature drop across coilmeasure the coil s dry bulb entering and leaving air temperatures (A and C). Temperature Drop Formula: (T Drop ) = A minus C. Step 3. Determine if fan needs adjustmentif the difference between the measured T Drop and the desired DT (T Drop DT) is within +3º, no adjustment is needed. See examples: Assume DT = 15 and A temp. = 72º, these C temperatures would necessitate stated actions: Cº T Drop DT = ºF ACTION 53º 19 15 = 4 Increase the airflow 58º 14 15 = 1 (within +3º range) no change 62º 10 15 = 5 Decrease the airflow Step 4. Adjust the fan speedsee indoor unit instructions to increase/decrease fan speed. Changing air flow affects all temperatures; recheck temperatures to confirm that the temperature drop and DT are within +3º. Figure 23. Checking Indoor Airflow over Evaporator Coil using Delta T Chart Setup for Checking and Adding Charge SETUP FOR CHARGING Connect the manifold gauge set to the unit s service ports (see figure 20): low pressure gauge to vapor service port high pressure gauge to liquid service port Close manifold gauge set valves. Connect the center manifold hose to an upright cylinder of HFC 410A. CALCULATING CHARGE If the system is void of refrigerant, first, locate and repair any leaks and then weigh in the refrigerant charge into the unit. To calculate the total refrigerant charge: Amount specified on nameplate Adjust amt. for variation in line set length (table 4) Additional charge specified per indoor unit match up (table 5) Total charge + + = Weigh in Charge 1. Recover the refrigerant from the unit. 2. Conduct leak check; evacuate as previously outlined. 3. Weigh in the unit nameplate charge plus any charge required for line set differences from 15 feet and any extra indoor unit match up amount per table 5. (If weighing facilities are not available, use the subcooling method.) Table 4. Charge per Line Set Lengths Liquid Line Set Diameter Oz. per 5 ft. (g per 1.5m) adjust from 15 ft. (4.6m) line set* 3/8 in. (9.5mm) 3 ounce per 5 ft. (85g per 1.5m) NOTE *If line length is greater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract this amount. Subcooling Charge Requirementsthese items are required for charging: Manifold gauge set connected to unit. Thermometers for measuring outdoor ambient, liquid line, and vapor line temperatures. When to use cooling modewhen outdoor temperature is 60 F (15 C) and above, use cooling mode to adjust charge. When to use heating modewhen the outdoor temperature is below 60 F (15 C), use the heating mode to adjust the charge. Adding Charge for Indoor Match UpTable 5 lists all the Lennox recommended indoor unit matches along with the charge levels for the various sizes of outdoor units. Page 15 XP14 SERIES

SATº LIQº SCº = Use cooling mode 60ºF (15ºC) Use heating mode Table 5. Adding Charge per Indoor Unit Match using Subcooling Method 1 Check the airflow as illustrated in figure 23 on page 15 to be sure the indoor airflow is as required. (Make any air flow adjustments before continuing with the following procedure.) 2 Measure outdoor ambient temperature; determine whether to use cooling mode or heating mode to check charge. 3 Connect gauge set. 4 Check Liquid and Vapor line pressures. Compare pressures with Normal Operating Pressures table 7, (Table 7 is a general guide. Expect minor pressure variations. Significant differences may mean improper charge or other system problem.) 5 Set thermostat for heat/cool demand, depending on mode being used: Using cooling modewhen the outdoor ambient temperature is 60 F (15 C) and above. Target subcooling values in table below are based on 70 to 80 F (21 27 C) indoor return air temperature; if necessary, operate heating to reach that temperature range; then set thermostat to cooling mode setpoint to 68ºF (20ºC). When pressures have stabilized, continue with step 6. Using heating modewhen the outdoor ambient temperature is below 60 F (15 C). Target subcooling values in table below are based on 65 75 F (18 24 C) indoor return air temperature; if necessary, operate cooling to reach that temperature range; then set thermostat to heating mode setpoint to 77ºF (25ºC). When pressures have stabilized, continue with step 6. 6 Read the liquid line temperature; record in the LIQº space. 7 Read the liquid line pressure; then find its corresponding temperature in the temperature/ pressure chart listed on page 18 and record it in the SATº space. 8 Subtract LIQº temp. from SATº temp. to determine subcooling; record it in SCº space. 9 Compare SCº results with table below, being sure to note any additional charge for line set and/or match up. 10 If subcooling value is greater than shown in table, remove refrigerant; if less than shown, add refrigerant. 11 If refrigerant is added or removed, repeat steps 5 through 10 to verify charge. 505244M 10/09 Page 16

Table 6. Air Handler/Coil Matchups and Target Subcooling INDOOR MATCHUPS Target Subcooling HeatingМCooling (+5ºF)ННН(+1ºF) *Add charge INDOOR MATCHUPS Target Subcooling HeatingМCooling (+5ºF)ННН(+1ºF) *Add charge INDOOR MATCHUPS Target Subcooling HeatingМCooling (+5ºF)ННН(+1ºF) *Add charge XP14 018 lb oz XP14 030 (Continued) lb oz XP14 042 (Continued) lb oz CBX27UH 018/024 13 7 0 8 CH33 42B 6 6 1 12 CR33 50/60C, 60D 26 6 0 4 CBX32MV 018/024 15 7 0 0 CR33 30/36A/B/C 30 8 0 8 CX34 62C, 62D 12 6 0 9 CBX40UHV 024 15 7 0 0 CX34 31A/B 11 6 1 6 CX34 49C 12 6 0 7 XP14 024 lb oz CBX26UH 024 25 7 0 0 CX34 38A/B S/N# 6007 and after CX34 38A/B Before S/N# 6007 6 6 2 3 CX34 60D 12 6 0 4 11 6 2 3 XP14 048 lb oz CBX27UH 018/024 15 8 1 2 CX34 43B/C 15 11 2 14 CBX26UH 048 8 7 1 9 CBX32M 018/024 16 8 0 14 XP14 036 lb oz CBX27UH 048 11 8 1 2 CBX32M 030 15 8 1 3 C33 44C 13 6 0 0 CBX32M 048, 060 11 8 1 2 CBX32MV 018/024 16 8 0 14 CBX26UH 036 26 5 0 0 CBX32MV 048 25 8 0 0 CBX32MV 024/030 15 8 1 2 CBX26UH 037 25 4 1 9 CBX32MV 060 11 8 1 2 CBX40UHV 024 16 8 0 14 CBX27UH 036 13 6 0 3 CBX40UHV 048 25 8 0 0 CBX40UHV 030 15 8 1 2 CBX32M 036 13 6 0 2 CBX40UHV 060 11 8 1 2 CH23 41 16 8 0 2 CBX32M 042 13 6 0 3 CBX32MV 068 10 7 1 12 CH33 25A 16 6 0 7 CBX32MV 036 13 6 0 3 CH23 68 20 9 2 9 CH33 42B 14 11 1 10 CBX32MV 048 11 8 2 5 CH33 50/60C 11 8 1 1 CH33 36A 16 8 1 0 CBX40UHV 036 13 6 0 3 CH33 62D 10 7 1 14 CH33 36C 16 8 0 4 CBX40UHV 042, 048 11 8 2 5 CH33 60D 11 8 0 0 CR33 30/36A/B/C 25 7 0 2 CH33 50/60C 11 8 2 5 CR33 50/60C 35 5 0 0 CX34 25A/B 16 8 0 14 CH33 44B 13 6 1 7 CR33 60D 37 6 0 0 CX34 31A/B 15 8 1 3 CH33 48B 13 6 1 8 CX34 62C, 62D 10 7 1 7 CX34 36A/B/C 16 8 1 8 CR33 50/60C 25 4 1 15 CX34 49D 11 8 0 14 CX34 38A/B S/N# 6007 and after CX34 38A/B before S/N# 6007 11 11 2 2 CR33 48B/C 25 5 0 9 CX34 60D 11 8 0 0 14 11 2 2 CX34 49C 13 6 2 4 XP14 060 lb oz XP14 030 lb oz CX34 43B/C, 50/60C 13 6 1 8 CBX26UH 048 12 7 1 0 CH23 41 11 6 0 8 CH23 51 6 6 1 12 CX34 38A/B S/N# 6007 and after CX34 38A/B before S/N# 6007 6 6 0 0 CBX26UH 060 14 4 0 0 13 6 0 0 CBX27UH 060 12 5 0 0 CBX26UH 024 30 8 0 6 XP14 042 lb oz CBX32M 048, 060 12 5 0 0 CBX26UH 030 29 8 2 3 CH23 68 20 9 0 13 CBX32MV 048, 060 12 5 0 0 CBX27UH 030 11 6 2 4 CBX26UH 042 27 6 0 0 CBX40UHV 048, 060 12 5 0 0 CBX32M 030 11 6 1 6 CBX27UH 042 12 6 0 8 CBX32MV 068 12 7 1 0 CBX32M 036 11 6 2 4 CBX32M 048 12 6 0 7 CH23 68 12 5 0 0 CBX32MV 024/030 11 6 1 6 CBX32MV 048 12 6 0 8 CH33 50/60C 12 5 0 0 CBX32MV 036 15 7 3 0 CBX40UHV 042, 048 12 6 0 8 CH33 62D 12 5 0 0 CBX40UHV 024, 030 11 6 1 6 CH33 43 12 6 0 7 CX34 62C, 62D 12 7 1 0 CBX40UHV 036 15 7 3 0 CH33 62D 12 6 0 10 C33 44C 11 6 2 3 CH33 50/60C 12 6 0 7 CH33 36C 11 3 0 0 CH33 60D 12 6 0 4 *Add charge = Extra matchup amount required in addition to charge indicated on Heat Pump nameplate (remember to also add any charge required for line set differences from 15 feet). SN indicates serial number. Page 17 XP14 SERIES