Installation Instructions (Cat. No. 1771-P7 Series D) To the Installer This document provides you with the following information: For this information See page compliance European Union Directive 1 preparing to install the power supply 2 installing the power supply 3 connecting ac power to the power supply 7 troubleshooting 8 power ratings 9 mounting dimensions 9 specifications 10 UL/CSA hazardous location approval 11 Compliance to European Union Directives The series D version of this product is marked with the ÎÎ logo, indicating that this version complies with the European Union Directives noted below. It is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives. EMC Directive This product is tested to meet Council Directive 89/336/EEC Electromagnetic Compatibility (EMC) and the following standards, in whole or in part, documented in a technical construction file: EN 50081-2 EMC Generic Emission Standard, Part 2 Industrial Environment EN 50082-2 EMC Generic Immunity Standard, Part 2 Industrial Environment This product is intended for use in an industrial environment.
2 AC (120/220V) 16A Power Supply Low Voltage Directive This product is also tested to meet Council Directive 73/23/EEC Low Voltage, by applying the safety requirements of EN 61131 2 Programmable Controllers, Part 2 Equipment Requirements and Tests. For specific information that the above EN requires, see the appropriate sections in this publication, as well as the following Allen-Bradley publications: Industrial Automation Wiring and Grounding Guidelines (for noise immunity), publication 1770-4.1 Guidelines for Handling Lithium Batteries, publication AG-5.4 Automation Systems Catalog, publication B111 Prepare for Installation The 1771-P7 power supply can power one 1771-A1B, -A2B, -A3B, -A3B1, or -A4B I/O chassis when used with any adapter module or programmable controller (Mini-PLC-2/02, Mini-PLC-2/05, Mini-PLC-2/16, Mini-PLC-2/17, or PLC-5 family processor) that does not have an internal power supply. Important: The power supply is not compatible with the 1771-A1, -A2, or -A4 I/O chassis. ATTENTION: The 1771-P7 is a stand-alone power supply. Do not connect it in parallel with any other power supply. Connecting it in parallel could result in processor memory loss or injury due to unexpected machine operation. ATTENTION: Under some conditions, electrostatic discharge can degrade performance or damage system components. Observe the following precautions to guard against electrostatic damage: Touch a grounded object to rid yourself of charge before handling a module. Do not touch the backplane connector or connector pins. When not in use, keep modules in their static-shield bags.
AC (120/220V) 16A Power Supply 3 Before installing the power supply, you should: mount the I/O chassis that the power supply will be connected to. See the Universal I/O Chassis Installation Data (1771-2.210) for information on mounting the I/O chassis. set the power supply configuration jumper on the I/O chassis. The 1771-P7 is an external power supply. Set the configuration jumper to the N position. Using Power Supply Module in the Chassis? 12620-I Install the 1771-P7 and Connect Backplane Power The power supply has a D-shell power connector that provides power to the I/O chassis backplane. A1 backplane common A2 backplane +5V dc 1 no connection 2 backplane processor enable 3 backplane +5V dc sense 4 backplane signal ground sense 5 no connection A1 3 4 5 A2 2 1 bottom view of power supply 13445 If you have this I/O chassis Use this power cable To connect a 1771-P7 mounted 1771-A3B 1771-CP2 within 1.52m (5ft) of the I/O chassis 1771-A1B, 1B -A2B, -A3B1, or -A4B 1771-CP1 within 0.32m (1.04ft) on the left-side of the I/O chassis 1771-CP2 within 1.52m (5ft) of the I/O chassis 1771-CP3 (right angle connector) within 1.68m (5.5ft) of the I/O chassis
4 AC (120/220V) 16A Power Supply If you are mounting the power supply Go to on the left side of a panel-mounted I/O chassis next section separately from an I/O chassis page 6 Attaching to a Panel-mounted I/O Chassis 1. Attach the mounting screws to the side of the I/O chassis as shown: ATTENTION: Use the mounting screws provided with the 1771-P7. Longer screws may intrude into the I/O chassis and interfere with module insertion. lockwasher shoulder washer large screw Tighten this screw. left-side of I/O chassis two small screws and lockwashers 2. Connect the power cable (ordered separately) to the D-shell connector on the I/O chassis and tighten the connector screws. D-shell connector connector screws left-side of I/O chassis 1771-CP1 cable 13447
AC (120/220V) 16A Power Supply 5 3. Slide the power supply onto the left side of the chassis, as shown: 1771-P7 Place keyhole slot over large screw on I/O chassis. Slide power supply down. left side I/O chassis Make sure mounting brackets are behind the small screws. 13448 4. Tighten the small screws to secure the power supply to the I/O chassis. 1771-P7 left side I/O chassis small screws 12629-I 5. Attach the other end of the power cable to the D-shell connector on the bottom of the power supply and tighten the connector screws. 1771-P7 left side I/O chassis D-shell connector connector screws 1771-CP1 cable 13449
6 AC (120/220V) 16A Power Supply Mounting the Power Supply Separately When mounted separately, the power supply may be mounted above or next to the I/O chassis. It may not be mounted below, since it is necessary to allow convection cooling of both the power supply and the I/O chassis. A minimum vertical distance of 6 inches (15.2cm) should be maintained. 1. Mount the power supply vertically, above and within the specified cable-feet (for your cable) of the D-shell connector on the I/O chassis. 1771-P7 Use the rear mounting flanges on the power supply to mount it to a panel. 15.2cm (6 ) Allow for a generous bend of the 1771-CP2 or 1771-CP3 cable to reduce stress on the connectors mounted on the chassis and the power supply. 12621-I 2. Connect one end of the power cable (ordered separately) to the D-shell connector located on the bottom of the power supply and tighten the connector screws. 1771-P7 connector screws 1771 CP2 or 1771-CP3 cable 12622-I
AC (120/220V) 16A Power Supply 7 3. Connect the other end of the power cable to the D-shell connector on the I/O chassis and tighten the connector screws. 1771-A1B, -A2B, -A3B1, -A4B I/O chassis 1771-A3B I/O chassis 1771 CP2 1771 CP3 12623-I 12624-I Connect ac Power Source to the Power Supply The power supply operates on nominal120v ac or 220V ac input source. 1. Make sure the power switch is set to OFF. ON POWER OFF 2. Use a 1/8 slotted screwdriver to set the input-voltage selector switch. ATTENTION: To avoid damaging the power supply, do not place the screwdriver blade more than 3/8 into the switch slot. 115V For an input voltage of Set the voltage selector switch to 12625-I 97 to 132V ac 115 position 115V 195 to 264V ac 230 position 230V
8 AC (120/220V) 16A Power Supply 3. Connect the ac power line to the terminal strip on the power supply. ATTENTION: You must connect a 14 AWG wire from the GND terminal to the ground bus to provide an adequate safety ground. ac power connectors Connect high side of the line power ➀ low side of the line power central ground bus (earth ground) L1 L2/N GND Line 1 Line 2 or neutral Ground Bus ac power (customer supplied) 14 AWG ➀ A 3A 250V normal-blow fuse protects the input line L1 from drawing more than 3 amperes. Grounding electrode conductor 12626-I Troubleshooting P/S Active The power supply has a green P/S ACTIVE LED that provides status indication during power supply operation. Normal operation If indicator is Then on off it may be due to: input voltage not within specified range blown fuse overcurrent 12627-I Important: If a shutdown condition occurs, wait 15 seconds before attempting to apply power. For additional assistance, contact your local Allen-Bradley representative.
AC (120/220V) 16A Power Supply 9 Power Ratings Use these graphs to determine your: cooling requirements power cost transformer size (unless the transformer manufacturer has a recommended multiplier for sizing a transformer for an ac-to-dc power supply) Backplane Load Current (Amps) 16 12 8 4 0 20 60 100 140 180 Apparent Power (VA) 16 12 8 4 0 0 30 60 90 120 Real Power (Watts) 16 12 8 4 0 0 75 150 225 300 Transformer Sizing (VA) = Real Power (Watts) x 2.5 Mounting Dimensions 46mm 1.83 114mm (4.49 ) 315mm (12.40 ) 293mm (11.53 ) Depth is 159mm (6.25 ) 12628-I
10 AC (120/220V) 16A Power Supply Specifications Nominal Input Voltage/Current 120V ac @ 2.0A 220V ac @ 1.0A Input Voltage Range 120V ac: 97-132V ac 220V ac: 195-264V ac Input Power (Real/Apparent) 108 Watts/176VA External Transformer Frequency Range 270VA at full load 47-63Hz Isolation Voltage 2500V dc for 1s 1800V ac (rms) for 1s Output Voltage 5.06V dc ±3.8% Output Current Power Loss Time Delay Input Power to Processor Disable Fuse Screw Torque Weight Dimensions (H x W x D) Environmental Conditions Operating Temperature Storage Temperature Relative Humidity Cables 1771-CP1 1771-CP2 1771-CP3 Agency Certification (when product or packaging is marked) 16A max @ 5V dc 13.6ms ±2.9ms input power to chassis ground 3A, 250V 3AG normal blow (Bussmann AGC 3 Littelfuse 312003) 12 pound-inch 1.95kg (4.3 lbs.) 315mm x 115mm x 159mm (12.40 x 4.53 x 6.25 ) 32 to 140 F (0 to 60 C) 40 to 185 F ( 40 to 85 C) 5 to 95%, non-condensing 0.32m (1.04ft) connects panel-mounted I/O chassis to chassis mounted 1771-P7 1.52m (5ft) connects rack-mounted I/O chassis to remote 1771-P7 1.68m (5.5ft) connects panel-mounted I/O chassis to remote 1771-P7 CSA certified CSA Class I, Division 2 Groups A, B, C, D certified UL listed CE marked for all applicable directives
AC (120/220V) 16A Power Supply 11 CSA Hazardous Location Approval CSA certifies products for general use as well as for use in hazardous locations. Actual CSA certification is indicated by the product label as shown below, and not by statements in any user documentation. Example of the CSA certification product label Approbation d utilisation dans des emplacements dangereux par la CSA La CSA certifie les produits d utilisation générale aussi bien que ceux qui s utilisent dans des emplacements dangereux. La certification CSA en vigueur est indiquée par l étiquette du produit et non par des affirmations dans la documentation à l usage des utilisateurs. Exemple d étiquette de certification d un produit par la CSA To comply with CSA certification for use in hazardous locations, the following information becomes a part of the product literature for CSA-certified Allen-Bradley industrial control products. This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D, or non-hazardous locations only. The products having the appropriate CSA markings (that is, Class I Division 2, Groups A, B, C, D), are certified for use in other equipment where the suitability of combination (that is, application or use) is determined by the CSA or the local inspection office having jurisdiction. Important: Due to the modular nature of a PLC control system, the product with the highest temperature rating determines the overall temperature code rating of a PLC control system in a Class I, Division 2 location. The temperature code rating is marked on the product label as shown. Temperature code rating Pour satisfaire à la certification de la CSA dans des endroits dangereux, les informations suivantes font partie intégrante de la documentation des produits industriels de contrôle Allen-Bradley certifiés par la CSA. Cet équipement convient à l utilisation dans des emplacements de Classe 1, Division 2, Groupes A, B, C, D, ou ne convient qu à l utilisation dans des endroits non dangereux. Les produits portant le marquage approprié de la CSA (c est à dire, Classe 1, Division 2, Groupes A, B, C, D) sont certifiés à l utilisation pour d autres équipements où la convenance de combinaison (application ou utilisation) est déterminée par la CSA ou le bureau local d inspection qualifié. Important: Par suite de la nature modulaire du système de contrôle PLC le produit ayant le taux le plus élevé de température détermine le taux d ensemble du code de température du système de contrôle d un PLC dans un emplacement de Classe 1, Division 2. Le taux du code de température est indiqué sur l étiquette du produit. Taux du code de température Look for temperature code rating here The following warnings apply to products having CSA certification for use in hazardous locations. Le taux du code de température est indiqué ici Les avertissements suivants s appliquent aux produits ayant la certification CSA pour leur utilisation dans des emplacements dangereux. ATTENTION: Explosion hazard Substitution of components may impair suitability for Class I, Division 2. Do not replace components unless power has been switched off or the area is known to be non-hazardous. Do not disconnect equipment unless power has been switched off or the area is known to be non-hazardous. Do not disconnect connectors unless power has been switched off or the area is known to be non-hazardous. Secure any user-supplied connectors that mate to external circuits on an Allen-Bradley product using screws, sliding latches, threaded connectors, or other means such that any connection can withstand a 15 Newton (3.4 lb.) separating force applied for a minimum of one minute. AVERTISSEMENT: Risque d explosion La substitution de composants peut rendre ce matériel inacceptable pour lesemplacements de Classe I, Division 2. Couper le courant ou s assurer quel emplacement est désigné non dangereux avant de remplacer lescomposants. Avant de débrancher l équipement, couper le courant ou s assurer que l emplacement est désigné non dangereux. Avant de débrancher les connecteurs, couper le courant ou s assurer que l emplacement est reconnu non dangereux. Attacher tous connecteurs fournis par l utilisateur et reliés aux circuits externes d un appareil Allen-Bradley à l aide de vis, loquets coulissants, connecteurs filetés ou autres moyens permettant aux connexions de résister à une force de séparation de 15 newtons (3,4 lb. - 1,5 kg) appliquée pendant au moins une minute. Le sigle CSA est la marque déposée de l Association des Standards pour le Canada. PLC est une marque déposée de Allen-Bradley Company, Inc. CSA logo is a registered trademark of the Canadian Standards Association PLC is a registered trademark of Allen-Bradley Company, Inc. PLC-2/02, PLC-2/05, PLC-2/16, and PLC-2/17 are trademarks of Allen-Bradley Company, Inc.
12 AC (120/220V) 16A Power Supply Allen-Bradley, a Rockwell Automation Business, has been helping its customers improve productivity and quality for more than 90 years. We design, manufacture and support a broad range of automation products worldwide. They include logic processors, power and motion control devices, operator interfaces, sensors and a variety of software. Rockwell is one of the world s leading technology companies. Worldwide representation. Argentina Australia Austria Bahrain Belgium Brazil Bulgaria Canada Chile China, PRC Colombia Costa Rica Croatia Cyprus Czech Republic Denmark Ecuador Egypt El Salvador Finland France Germany Greece Guatemala Honduras Hong Kong Hungary Iceland India Indonesia Ireland Israel Italy Jamaica Japan Jordan Korea Kuwait Lebanon Malaysia Mexico Netherlands New Zealand Norway Pakistan Peru Philippines Poland Portugal Puerto Rico Qatar Romania Russia CIS Saudi Arabia Singapore Slovakia Slovenia South Africa, Republic Spain Sweden Switzerland Taiwan Thailand Turkey United Arab Emirates United Kingdom United States Uruguay Venezuela Yugoslavia Allen-Bradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444 PN 955127 38 Copyright 1997 Allen-Bradley Company, Inc. Printed in USA